黏土-灰岩地基中的孔压现场测试与分析

    Field test and analysis of pore pressure in clay-limestone foundation

    • 摘要: 地下结构抗浮设计关键要明确基底孔压变化规律,依托地铁项目制定监测方案,在场地周边设置水位和气象监测点,在车站基底设置孔压计,进行为期两年的实时监测,得到从车站施工到运营全过程的黏土-灰岩地基中的孔压,并对孔压影响因素展开分析。测试与分析结果表明,基底各点孔压对降水和降雨响应及时,监测区内的降水可有效消减基底孔压,监测区外的降水会因渗透损失而形成孔压折减,折减系数均值在0.14~0.70之间变化;停止降水后,随着水位回升和各测点间水力连通,孔压接近静水压力,折减系数均值在0.87~0.98之间变化;降雨会增大孔压大小,且增幅受降雨量和降雨时期影响,暴雨可致使孔压最大达到静水压力的1.03倍,故有必要设置一定的抗浮安全系数。

       

      Abstract: The key to anti-floating design of underground structures lies in clarifying the variation pattern of pore pressure. Relying on the subway project, a monitoring plan was formulated, with water level and meteorological monitoring points set up around the site, and pore pressure gauges installed at the base of the station. Real-time monitoring was conducted for a period of two years, obtaining the pore pressure in the clay-limestone foundation throughout the entire process from station construction to operation, and analyzing the factors affecting pore pressure. The test and analysis results indicate that the pore pressure at various points of the basement responds promptly to precipitation and rainfall. Precipitation within the monitoring area can effectively reduce the pore pressure, while precipitation outside the monitoring area will form a reduction in pore pressure due to infiltration loss, with an average reduction coefficient ranging from 0.14 to 0.70. After the cessation of precipitation, as the water level rose and hydraulic connectivity between various measuring points was established, the pore pressure approached hydrostatic pressure, with the mean value of the reduction factor varying between 0.87 and 0.98. Rainfall will increase the magnitude of pore pressure, and the increase is affected by the amount and duration of rainfall. A rainstorm can cause the pore pressure to reach up to 1.03 times the hydrostatic pressure, so it is necessary to set a certain anti-floating safety factor.

       

    /

    返回文章
    返回